①. 工作人(ren)員經常進入(ru)的通行管(guan)溝(gou)(gou)應(ying)有照明設備和良好的通風。人(ren)員在管(guan)溝(gou)(gou)內工作時,空氣溫(wen)度不(bu)得超過40℃。
②. 通行(xing)管(guan)(guan)溝(gou)應設(she)(she)事(shi)故(gu)人孔(kong)(kong)。設(she)(she)有(you)蒸汽管(guan)(guan)道(dao)的通行(xing)管(guan)(guan)溝(gou),事(shi)故(gu)人孔(kong)(kong)間(jian)距應不大(da)于100m;熱水管(guan)(guan)道(dao)的通行(xing)管(guan)(guan)溝(gou),事(shi)故(gu)人孔(kong)(kong)間(jian)距應不大(da)于400m。
③. 整體混凝土結(jie)構的通(tong)行(xing)管(guan)溝,每隔200m宜(yi)設一(yi)個(ge)安(an)(an)裝孔(kong)。安(an)(an)裝孔(kong)寬度(du)應(ying)不小于0.6m且大(da)于管(guan)溝內最大(da)一(yi)根管(guan)道的外徑加0.1m,其長度(du)至少(shao)應(ying)保(bao)證(zheng)6m長的管(guan)子(zi)進入管(guan)溝。當(dang)需要考慮設備進出時(shi),安(an)(an)裝孔(kong)寬度(du)還應(ying)滿足(zu)設備進出的需要。